Troubleshooting the Underfloor Heating System

Our underfloor heating systems are not "Rocket Science" and operate in a relatively simple way. Hot water from the primary heat source is blended with the return water in the manifold by means of the thermostatic valve and secondary manifold pump before being circulated around the floor loops. Our systems include air temperature control to all rooms via a dial thermostat or Programmable thermostat. These in turn operate actuators on the manifold controlling single or multiple loops of pipe work depending on room size. When using a wiring/control centre any of the room thermostats can call for heat from the primary heat source via its relays thus providing the nessacery boiler interlock to conform to Part L BUILDING REGULATIONS.

Most problems experienced are related to wiring and the central heating system it is being attached to. We cannot take responability for the design of the system supplying the UFH. It is recommended that a competent heating engineer is employed who has the knowledge of combining underfloor heating with heat sources and hot water systems and a registered electrician who understands controls.

Unless a CAD design has been undertaken by WundaFloor there can be design problems with regard to the limitations of UFH and its suitability for the purpose intended.

Primary Checks

Electrical
  • Is there an electrical supply and is it ON?
  • Are there any fuses that have blown and need replacing?
  • Are any components overloaded?
  • Is everything wired correctly?
Plumbing
  • Is the boiler/heat source firing?
  • Is there a primary pump and is it running? (Manifold pump is only for underfloor loops and not for flow too and from heat source).
  • Is primary pipe work from heat source adequately sized?
  • Is there a motorized valve for the underfloor circuit and is it open?
Flowchart Diagram


From this point onwards it is assumed that the heat source is being called for heat and being pumped to the manifold.

Manifolds and Loops

No heat in the manifold
  • Is the pump running?
  • Is the thermostatic valve set at correct temperature: 45°C for screed / 65°C for suspended floors? Temporarily remove thermostat from valve to establish valve opens and lets hot water enter the manifold. Do not leave off as damage could occur to the floor if over heated. If flow gauges are showing circulation there could be a blockage in feed/ return to the manifold.
  • Is return valve fully open (bottom right-hand side)? Turn the valve anti-clockwise to open.
  • Is by-pass valve only open 2 turns (factory set)?
Manifold hot but no heat in loops
  • Is the pump running? Check the speed.
  • Are the flow gauges showing any flow? To open, turn anticlockwise.
  • Are the actuators on return bar open (warm to the touch)? If not, check room thermostat is calling for heat or temporally remove actuator to establish flow thru that loop.
  • Is there at least 7°C difference between Flow bar temperature and return bar temperature?
  • There could be air trapped in the loops, which will require purging. Shut down all but the problem loop to concentrate the pump pressure and force out the air. This will be heard running through the pump and the flow gauge will flutter.
Uncontrollable room temperatures

This is when the manifold appears to be functioning correctly and flow rates seem correct but particular rooms do not heat up.

  • This invariably means that rooms are not matched with there room thermostat, actuator and loop/s. between the first and second fix the potential for room loops and their thermostats to get mixed up is quite high. The only logical way of sorting this out is from cold. Start with one room at a time, turning on the room thermostat and checking that its floor warms up. This could take an hour before moving to the next room. Clearly mark the loops and actuator/s for future reference.
  • Floor covering provides too much thermal resistance to allow heat transfer and therefore output.
System too noisy

These tend to be installation and commissioning problems which are sorted out with good workmanship.

  • All pumps will produce low level noise and therefore should not be installed in areas of sensitivity but with careful installation practices can be reduced to a barely audible hum. Try to avoid mounting on a stud wall with only plasterboard walls as this tends to amplify any noise. The use of rubber isolation mountings on brackets etc can help.
  • Unless the system has been filled as instructed in the installation manuals the potential for trapped air is quite high. This air passing thru valves and pumps will not only produce noise but also promote corrosion. It is a condition of our guarantee that the system is correctly dosed with inhibitor for both the above reasons. An untreated system will quickly discolour the flow gauge sight glass, these can be easily cleaned by shutting valve (clockwise) and while holding shut undo glass anticlockwise, clean and replace.
  • The pump should be set to the lowest speed to achieve the design flow rates; this will save on energy and noise.
  • Pumps on the primary side of the system should also be checked to reduce noise at the manifold. It is also recommended to have a primary system by-pass fitted (now included in a lot of current system boilers).
Water leaks

It is very rare to get leaks in an underfloor heating system after the construction process has ended. As there are no joins in the floor most leaks are at the manifold and are generally fixed by tightening. Leaks in pipe work are normally found by a damp patch and repair couplings for 16mm MLC pipe can be purchased from Wundafloor. Do not keep topping up a leaking system for a long period as this reintroduces fresh un-inhibited water and air into the system.



Wundafloor offer cost effective Underfloor Heating systems for all Renovation and New Build projects.   Wundafloor, Hawthorn, Crick, South Wales, NP26 5UT. Tel: 01291 634 145

Floor Heating Solutions | Renovations | New Build | Bespoke Solutions | Heating FAQ | Floor Heating Coverings | Cost Effective Floor Heating | Bathroom Floor Heating | Bedroom Floor Heating | Conservatory Floor Heating | Dining Room Floor Heating | Extension Floor Heating | Garage Conversion Floor Heating | Hall Floor Heating | Kitchen Floor Heating | Living Room Floor Heating | Loft Conversion Floor Heating | Lounge Floor Heating | Renovations Floor Heating | Shower Room Undertile Heating | Study Floor Heating | Utility Floor Heating | Links | Help & Advice | About Us | Contact Us